Abstract
This report presents the 丘ndings of a field study of thermal com 丘)rt and thermal environment in 30 detached houses in Hyogo , 30 apartment houses in Osaka , Japan. A total of 70 subjects provided 459 sets of data f ()r summer , each accompanied by indoor climatic measurements . The sample of subjects consisted mostly of housewifb . The average clothing insulation levels were O28clo . The average metabolic rate was 1 . 3met . Thermal neutrality , according to responses on the ASHRAE seven ・ point sensation scale , occurred at 27 . 6℃ . The Operative temperature corresponding to the accepted thermal environment by 80 % ofthe occupants is under 28 . 4℃ .