Fast Calculation of Field Currents and Reactances for Doubly Fed Generators With Rotor Duct Pieces
Authors:
- K. ShimaKSK. Shima
- K. IdeKIK. Ide
- M. TakahashiMTM. Takahashi
- M. OkadaMOM. Okada
- O. NaguraONO. Nagura
- 23 October 2006
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 42 (11) , 3730-3736
Abstract
Doubly fed generators have been used as adjustable-speed pumped-storage generator motors and wind turbine generators. Accurate determination of field currents and reactances is important for the design of these machines. We propose a calculation method to obtain the field currents and reactances of machines with rotor duct pieces under any steady-state balanced load condition. The method links two-dimensional static finite-element analysis (FEA) with an approximate calculation to consider three-dimensional (3-D) skin effect in the duct pieces. Its advantage is that the computational time is much smaller than 3-D transient FEA when the slip frequency is not zero. The method will contribute to improvement of the design of doubly fed generators with rotor duct pieces. It was applied to a 395 MVA machine, and the calculated field currents agreed well with the measurements. Variation in the reactances due to saturation is also discussedKeywords
This publication has 14 references indexed in Scilit:
- Successful achievement in a variable speed pumped storage power system at Yagisawa power plant2002
- Finite-element calculation of leakage inductances of a saturated salient-pole synchronous machine with damper circuitsIEEE Transactions on Energy Conversion, 2002
- Optimal control of power unit with doubly fed machine2002
- Doubly Fed Induction Generator Systems for Wind Turbines: A Viable Alternative to Adjust Speed over a Wide Range at Minimal CostIEEE Industry Applications Magazine, 2002
- Calculation of leakage inductances of a salient-pole synchronous machine using finite elementsIEEE Transactions on Energy Conversion, 1999
- Design and dynamic response characteristics of 400 MW adjustable speed pumped storage unit for Ohkawachi Power StationIEEE Transactions on Energy Conversion, 1996
- Transient state analysis of a doubly-fed induction generator under three phase short circuitIEEE Transactions on Energy Conversion, 1991
- Finite Element Modeling of Large Turbine Generators; Calculations Versus Load Test DataIEEE Transactions on Power Apparatus and Systems, 1981
- An Adjustable Speed Synchronous Machine for Hydroelectric Power ApplicationsIEEE Transactions on Power Apparatus and Systems, 1981
- Simulation for Design Purposes of Magnetic Fields in Turbogenerators with Symmetrical and Asymmetrical Rotors Part I-Model Development and Solution TechniqueIEEE Transactions on Power Apparatus and Systems, 1972