Active and Reactive Power Injection Strategies for Three-Phase Four-Wire Inverters During Symmetrical/Asymmetrical Voltage Sags
- 14 January 2019
- journal article
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 55 (3) , 2347-2355
Abstract
Electric grid codes are expected to change in near future to accommodate an increased number of distributed generation units in the distribution power system without impairing its power quality. It is desired that the generators remain connected during voltage sags and provide ancillary services, such as voltage and reactive power control, ensuring the operational stability of the power system. This paper explores how the existing strategies for active and reactive power injection impact the operation of grid-tied inverters in terms of required power, current flowing and reduction of active power delivery during the voltage sags. Such inputs are relevant to properly size converters for operation under fault events. In addition, this paper contributes to devise ${1}$ ) constant peak current control, ${2}$ ) constant active current control and ${3}$ ) constant average active power control strategies for three-phase four-wire grid-tied inverters considering the natural (abc) reference frame. The design and implementation of the investigated power injection strategies are discussed, and their effectiveness and technical viability are analyzed through dynamic computational simulations under symmetrical/asymmetrical voltage sags, and variation of the short-circuit ratio.
Keywords
Funding Information
- Minas Gerais Research Foundation—FAPEMIG (02518-16)
- Brazilian government agency
- Graduate School—CAPES
This publication has 20 references indexed in Scilit:
- Control Strategy to Maximize the Power Capability of PV Three-Phase Inverters During Voltage SagsIEEE Transactions on Power Electronics, 2015
- Wide-Scale Adoption of Photovoltaic Energy: Grid Code Modifications Are Explored in the Distribution GridIEEE Industry Applications Magazine, 2015
- Reactive Power Control for Distributed Generation Power Plants to Comply With Voltage Limits During Grid FaultsIEEE Transactions on Power Electronics, 2014
- Reactive Power Injection Strategies for Single-Phase Photovoltaic Systems Considering Grid RequirementsIEEE Transactions on Industry Applications, 2014
- Low-Voltage Ride-Through of Single-Phase Transformerless Photovoltaic InvertersIEEE Transactions on Industry Applications, 2013
- Control Scheme for Photovoltaic Three-Phase Inverters to Minimize Peak Currents During Unbalanced Grid-Voltage SagsIEEE Transactions on Power Electronics, 2012
- Fault ride through requirements and measures of distributed PV systems in Japan2012
- Single-phase to three-phase four-leg converter applied to distributed generation systemIET Power Electronics, 2010
- Comparison of Control Strategies for Shunt Active Power Filters in Three-Phase Four-Wire SystemsIEEE Transactions on Power Electronics, 2007
- Three-dimensional space vector modulation for four-leg voltage-source convertersIEEE Transactions on Power Electronics, 2002