Abstract
A cross-sectional multicenter survey of Italian hotels was conducted to investigate Legionella spp. contamination of hot water. Chemical parameters (hardness, free chlorine concentration, and trace element concentrations), water systems, and building characteristics were evaluated to study risk factors for colonization. The hot water systems of Italian hotels were strongly colonized by Legionella ; 75% of the buildings examined and 60% of the water samples were contaminated, mainly at levels of ≥10 3 CFU liter −1 , and Legionella pneumophila was the most frequently isolated species (87%). L. pneumophila serogroup 1 was isolated from 45.8% of the contaminated sites and from 32.5% of the hotels examined. When a multivariate logistic model was used, only hotel age was associated with contamination, but the risk factors differed depending on the contaminating species and serogroup. Soft water with higher chlorine levels and higher temperatures were associated with L. pneumophila serogroup 1 colonization, whereas the opposite was observed for serogroups 2 to 14. In conclusion, Italian hotels, particularly those located in old buildings, represent a major source of risk for Legionnaires' disease due to the high frequency of Legionella contamination, high germ concentration, and major L. pneumophila serogroup 1 colonization. The possible role of chlorine in favoring the survival of Legionella species is discussed.Keywords
This publication has 54 references indexed in Scilit:
- Intracellular Proliferation of Legionella pneumophila in Hartmannella vermiformis in Aquatic Biofilms Grown on Plasticized Polyvinyl ChlorideApplied and Environmental Microbiology, 2004
- Pan-European Study on Culture-Proven Legionnaires' Disease: Distribution of Legionella pneumophila Serogroups and Monoclonal SubgroupsEuropean Journal of Clinical Microbiology & Infectious Diseases, 2002
- Legionella and Legionnaires' Disease: 25 Years of InvestigationClinical Microbiology Reviews, 2002
- Safe hot tap water and the risk of scalds and legionella infectionInjury Prevention, 2002
- An Outbreak of Travel‐Associated Legionnaires Disease and Pontiac Fever: The Need for Enhanced Surveillance of Travel‐Associated Legionellosis in the United StatesThe Journal of Infectious Diseases, 2002
- LegionellaSurveillance: Political and Social Implications—A Little Knowledge Is a Dangerous ThingThe Journal of Infectious Diseases, 2002
- Barriers to safe hot tap water: results from a national study of New Zealand plumbersInjury Prevention, 2001
- Detection of Legionellae in Hospital Water Samples by Quantitative Real-Time LightCycler PCRApplied and Environmental Microbiology, 2001
- Survey of ground, surface, and potable waters for the presence of Legionella species by EnviroAmpR PCR Legionella Kit, culture, and immunofluorescent stainingWater Research, 1997
- Measures of the Amount of Ecologic Association Between SpeciesEcology, 1945