Modeling and Real-time Simulation of Internal Faults in Turbogenerators
Authors:
- 21 August 2009
- journal article
- research article
- Published by Taylor & Francis in Electric Power Components and Systems
- Vol. 37 (9) , 957-969
Abstract
When an internal fault occurs in the lap-connected windings of turbogenerators, the symmetry between the parallel windings is broken, and different currents then flow because unsymmetrical magnetic linkage exists between the stator windings. The aim of this article is to present a real-time simulation model to investigate the internal fault currents in large turbogenerators with lap windings. This model is based on a modified winding function approach, where the machine inductances are calculated directly from the machine winding distribution. The calculation of the machine inductances are made easier by the use of machine electrical parameters instead of geometrical parameters. The simulation results have been obtained for different cases of internal faults. By using simulated internal fault data, a suitable numerical protection scheme for turbogenerators can be developed.Keywords
This publication has 13 references indexed in Scilit:
- A New Model of Synchronous Machine Internal Faults Based on Winding DistributionIEEE Transactions on Industrial Electronics, 2006
- Modeling and experimental validation of internal faults in salient pole synchronous machines including space harmonicsMathematics and Computers in Simulation, 2006
- Comprehensive simulation for faults in the stator windings of salient-pole synchronous generators2003
- Extension of winding function theory for nonuniform air gap in electric machineryIEEE Transactions on Magnetics, 2002
- Partitioning of synchronous machine windings for internal fault analysisIEEE Transactions on Energy Conversion, 2000
- Internal faults in synchronous machines. I. The machine modelIEEE Transactions on Energy Conversion, 2000
- Simulation of internal faults in synchronous generatorsIEEE Transactions on Energy Conversion, 1999
- Simulation and detection of dynamic air-gap eccentricity in salient-pole synchronous machinesIEEE Transactions on Industry Applications, 1999
- A novel method for modeling dynamic air-gap eccentricity in synchronous machines based on modified winding function theoryIEEE Transactions on Energy Conversion, 1998
- Digital Computer Calculation of Internal Fault Currents in a Synchronous MachineIEEE Transactions on Power Apparatus and Systems, 1968