A new method for analysing transformer condition using frequency response analysis
Authors:
- 1 July 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 19325517,p. 1-5
Abstract
In modern electrical transmission and distribution systems, power transformers are critical components within the network. In the event that a failure occurs in service, the impact can be far reaching. Not only causing extended outages, but costly repairs and potentially serious injury or fatality can result. The ageing transformer population increases the likelihood of failure so a reliable diagnostic tool is required to determine the remaining life of these assets. Frequency Response Analysis (FRA) has been growing in popularity in recent times as a tool to detect mechanical deformation within power transformers. However, because FRA relays on graphical analysis, it calls for an expert person to analyse the results. So far, there are no standard codes for FRA interpretation. This paper introduces an alternative method for analysing FRA results using the polar plot. Various types of faults have been simulated to assess its impact on the polar plot. The technique is easy to be implemented and automated so that the requirement for expert personnel can be eliminated.Keywords
This publication has 9 references indexed in Scilit:
- Realization of transformer winding network from sweep frequency response data2008
- Winding movement in power transformers: a comparison of FRA measurement connection methodsIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Power transformer life management2005
- Locating transformer faults through sensitivity analysis of high frequency modeling using transfer function approach2002
- Condition monitoring of power transformers in the Australian State of New South Wales using transfer function measurements2002
- Failures in power system transformers and appropriate monitoring techniques1999
- Parametric identification in potential transformer modellingIEEE Transactions on Power Delivery, 1992
- Potential Transformer Accuracy at 60HZ Voltages Above and Below Rating and at Frequencies Above 60 HZIEEE Transactions on Power Apparatus and Systems, 1981
- Mechanical stresses in transformer windingsJournal of the Institution of Electrical Engineers - Part II: Power Engineering, 1946