COMPARATIVE STABILITY ASSESSMENT OF GRID-FOLLOWING AND GRID-FORMING VSCS IN WEAK GRIDS

Authors:

Abstract
Under the high renewables penetrated and high power electronics dominated (“double high”) power systems, the wide-band oscillation problems of grid-following VSCs integrated into weak grids have brought severe challenges to the safe and stable operation of the system. To further investigate the stability of VSCs with different control schemes, namely the grid-following VSC and the grid-forming VSC, the small-signal sequence impedance models of the two types of VSCs are derived, and the sequence impedance characteristics of grid-following and grid-following VSCs are compared and analysed. The sequence impedance of the grid-following VSCs is primarily capacitive with high amplitude in the middle-frequency band while the sequence impedance of the grid-forming VSCs is mainly inductive with low amplitude. Based on the sequence impedance models of two types of VSCs, the stability of these two types of VSCs integrated into weak grids is also analysed. The results indicate that the grid-following VSCs are prone to sub/super synchronous oscillations in weak grids while the grid-forming VSCs are able to operate stably in weak grids. Finally, electromagnetic transient simulations are conducted to validate the sequence impedance models and the stability assessment.