Performance investigation of solar energy–aided compression-based building air conditioning strategies for variable climatic regions
Authors:
- 13 February 2024
- journal article
- research article
- Published by Springer Nature in Environmental Science and Pollution Research
- Vol. 31 (12) , 18672-18682
Abstract
Decoupling cooling and ventilation tasks with an existing air conditioning methodology are a promising performance-enhancement technology. In this direction, different configurations of a desiccant-integrated independent ventilation element attached to a conventional cooling system are proposed in this study. This work establishes a quantitative comparative performance analysis among the different process air cooling (obtained through desiccant dehumidification) techniques for three different climates, namely, hot-dry, tropical, and Mediterranean. EnergyPlus simulations have been executed on a small-scale office building of 400-m2 area. The building constructional details and other required simulation input parameters follow benchmark standards. As the chemical dehumidification increases, the process air, i.e., supply air temperature that cannot be sent directly to the room, needs to be cooled. Three approaches for process air cooling have been considered: direct expansion (DX) cooling coil, indirect evaporative cooling (IEC), and sensible heat recovery wheel (SHRW). A solar collector assembly with a supporting heating arrangement is coupled with desiccant unit for regeneration. Outdoor air is used for regeneration in the case of the DX cooling coil and IEC, whereas return air is used in the heat recovery wheel case. Annual simulation results reveal that the SHRW-aided case performs superior than DX coil case for the pertinent climatic conditions, with 9.6 to 45.01% of annual energy savings. For the IEC, energy consumption was 1.8 to 18.38% less than that of DX coil. Also, using return air in this best-suited case reduces the net thermal energy requirement for regeneration by 14.63 to 71.65% with respect to DX coil.Keywords
Funding Information
- Central Power Research Institute (RSOP/21-26/TH/7)
This publication has 21 references indexed in Scilit:
- Performance assessment of radiant cooling system integrated with desiccant assisted DOAS with solar regenerationApplied Thermal Engineering, 2017
- Experimental investigation of solar driven desiccant air conditioning system based on silica gel coated heat exchangerInternational Journal of Refrigeration, 2016
- Performance prediction of rotary solid desiccant dehumidifier in hybrid air-conditioning system using artificial neural networkApplied Thermal Engineering, 2016
- An experimental study of a novel integrated desiccant air conditioning system for building applicationsEnergy and Buildings, 2016
- Survey of hybrid liquid desiccant air conditioning systemsRenewable and Sustainable Energy Reviews, 2013
- Experimental investigation of a mini-type solar absorption cooling system under different cooling modesEnergy and Buildings, 2012
- U.S. Department of Energy Commercial Reference Building Models of the National Building Stock2011
- Performance analysis of liquid desiccant based air-conditioning system under variable fresh air ratiosEnergy and Buildings, 2010
- Energy consumption analysis on a dedicated outdoor air system with rotary desiccant wheelEnergy, 2007
- Analysis on a hybrid desiccant air-conditioning systemApplied Thermal Engineering, 2006