Response and Protection of DFIG System under Grid Fault
Authors:
- Xing ZhangXZXing Zhang
- Qin LiQLQin Li
- Shuying YangSYShuying Yang
- Zhen XieZXZhen Xie
- Renxian CaoRCRenxian Cao
- 1 January 2010
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 21574839,p. 1-5
Abstract
The use of doubly fed induction generators (DFIG) in large wind turbines has become quite common over the last few years. However, DFIG are very sensitive to grid disturbances, especially to voltage dips, therefore low voltage ridethrough(LVRT) technology for DFIG becomes one of the critical technology in the uninterrupted operation of wind power generation. In order to help the study of low voltage ride-through(LVRT) technology for DFIG, a detailed thoretical analysis of the dynamic behavior of DFIG during grid voltage drop and recovery has been proposed, and obtained the maximum instantaneous rotor voltage when the voltage drop and the maximum and minimum rotor voltage when voltage recovery, then given the relevant simulation waveform. At last, the method on crowbar design is proposed.Keywords
This publication has 4 references indexed in Scilit:
- Dynamic Behavior of the Doubly Fed Induction Generator During Three-Phase Voltage DipsIEEE Transactions on Energy Conversion, 2007
- Fault Ride-through Performance of Wind Turbine with Doubly Fed Induction Generator2007
- Modeling and control of wind-turbine used DFIG under network fault conditions2005
- Dynamic modeling of doubly fed induction generator wind turbinesIEEE Transactions on Power Systems, 2003