Economics of EHV High Phase Order Transmission
Authors:
- 1 November 1984
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-103 (11) , 3386-3392
Abstract
The economics of high phase order transmission (six or twelve phase lines) are compared to UHV three phase. The comparisons are developed from optimized line designs, based on realistic lifetime costs. Detailed structure designs were used in the study, with terminal equipment costs included to develop- a breakeven distance beyond which savings in the HPO transmission line offset any increased substation costs. This breakeven distance is typically only a few miles, i. e. much shorter than projected UHV lines. A sensitivity analysis allows the general conclusion to be drawn that high phase order is econocmically compettivei- with UHV. Additional advantages are that the HPO structures are significantly smaller, and the ROW probably significantly narrower.Keywords
This publication has 4 references indexed in Scilit:
- Mechanical And Electrical Characteristics Of EHV High Phase Order Overhead TransmissionIEEE Transactions on Power Apparatus and Systems, 1984
- High Phase Order - Ready for ApplicationIEEE Transactions on Power Apparatus and Systems, 1982
- Economic Incentives for Larger Transmission ConductorsIEEE Transactions on Power Apparatus and Systems, 1981
- High Phase Order Transmission--A Feasibility Analysis Part I--Steady State ConsiderationsIEEE Transactions on Power Apparatus and Systems, 1978