Attack Induced Common-Mode Failures on PLC-Based Safety System in a Nuclear Power Plant: Practical Experience Report
- 1 January 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 205-210
Abstract
This paper demonstrates attack induced common-mode failures on an industrial-grade (Tricon) Triple-Modular-Redundant PLC (programmable logic controller) and its impact in a Nuclear Power Plant settings. The attack exploits the fact that during the configuration phase the same control logic is downloaded to all three redundant modules. We describe how an attacker can exploit this vulnerability to embed malicious control logic and how to trigger the attack. The feasibility and the attack impact are evaluated on a testbed, which includes the Tricon PLC as part of a safety protection system in a simulated nuclear power plant.Keywords
This publication has 5 references indexed in Scilit:
- SABOT2012
- Trust No One Else: Detecting MITM Attacks against SSL/TLS without Third-Parties2012
- An Analysis on the Schemes for Detecting and Preventing ARP Cache Poisoning Attacks2007
- Reliability modeling of TMR computer systems with repair and common mode failuresMicroelectronics Reliability, 1981