Abstract
In this paper, we propose a generalized over-current (OC) and overload (OL) protection scheme for droop-controlled and directly voltage controlled (DVC) inverter-interfaced distributed energy resources (IIDERs) to be used for protection studies of alternating current (AC) islanded (autonomous) microgrids, and provide a management strategy during and after short circuit and consequent overloads. The fault is detected, and its type is discriminated by a new method that takes the advantages of both artificial neural networks (ANNs) and transient monitoring function (TMF). By using the proposed strategy, the output current magnitudes of DER units are limited, and after fault clearance, the microgrid is restored to its normal operating conditions. The proposed OC/OL protection scheme limits the output power of distributed energy resources (DERs). In this regard, a generalized fault model is presented, which considers the effect of the control system of IIDERs. This model exploits a current limiting strategy (CLS) that can be implemented in different reference frames to enhance microgrid fault ride-through (FRT) capability. Finally, to demonstrate effectiveness, accuracy, authenticity, and feasibility of the proposed OC/OL protection scheme along with TMF/ANN-based fault detection method and their desirable performance, offline digital time-domain simulations are done in MATLAB/ Simulink environment, and the results are experimentally verified by using OPAL-RT real-time digital simulator (RTDS).

This publication has 23 references indexed in Scilit: