Abstract
Steel fiber-reinforced concrete pipe (SFRCP) has many unique benefits over traditionally produced reinforced concrete pipe (RCP). SFRCP is now being evaluated and implemented into standards in North America. This paper provides research data on the manufacturing and performance of this product when compared to traditional RCP. The most widely accepted way to evaluate the structural performance of RCP is to conduct D-load testing. Evaluations will be presented on 48-inch and smaller diameters of SFRCP that were manufactured in accordance with ASTM C76 for Class III, B-wall pipe and tested in accordance with ASTM C497. The only variation in manufacturing was the substitution of zinc-coated steel fibers for all of the traditional welded wire reinforcement found in RCP. SFRCP performance was recorded continuously using pressure transducers and deflection gauges. Loads on the pipe were noted when SFRCP developed a 0.01-inch-wide crack and when the pipe's ultimate structural strength was reached. The load performance was then compared to set values found in ASTM C76 for a Class III RCP. The SFRCP demonstrated some unique benefits over traditional RCP, but it also highlighted the need to more closely structurally evaluate the loads at ultimate with respect to the 0.01-inch crack because testing showed decreases in typical safety factors associated with the relationship between these two performance criteria. An evaluation of the manufacturing and handling performance of SFRCP against traditional RCP was also evaluated with SFRCP, showing many significant performance benefits.