Analysis of energy efficiency of air handling unit with integrated air to air heat exchanger in heating mode
Authors:
Open Access
- 18 November 2020
- conference paper
- Published by EDP Sciences in E3S Web of Conferences
- Vol. 207, 01002
Abstract
Object of the present study is an experimental determination of energy efficiency parameters of air handling unit with integrated air to air heat exchanger: effectiveness of air to air heat exchanger, coefficient of performance and specific fan power of air handling unit. A daily performance of air handling unit is conducted. Effectiveness of supply side of air to air heat exchanger in range of 42.4 % to 52.5 % is received. Coefficient of performance in range of 1.50 to 2.08 and specific fan power of air handling unit in range of 1.39 kW/(m3/s) to 2.08 kW/(m3/s) are received. It was found experimentally that effectiveness of air to air heat exchanger depends on values of mass flow of supply and the exhaust air. High values of mass flow of the exhaust air responds to high effectiveness of supply side of air to air heat exchanger.Keywords
This publication has 5 references indexed in Scilit:
- Analysis of energy efficiency of air handling unit with integrated air to air heat exchanger in heating modeE3S Web of Conferences, 2020
- Modeling air-to-air plate-fin heat exchanger without dehumidificationApplied Thermal Engineering, 2018
- Designing an air-to-air heat exchanger dedicated to single room ventilation with heat recoveryBuilding Simulation, 2017
- VENTILATION SYSTEM WITH GROUND HEAT EXCHANGERJournal of Ecological Engineering, 2016
- Heat Transfer and Effectiveness Analysis of a Cross-Flow Heat Exchanger for Potential Energy Recovery Applications in Hot-Humid ClimateEnergy Research Journal, 2015