Electromagnetic Time Reversal as a Correlation Estimator: Improved Metrics and Design Criteria for Fault Location in Power Grids
- 12 June 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Electromagnetic Compatibility
- Vol. 62 (2) , 598-611
Abstract
Recently published papers have proved the effectiveness of electromagnetic time reversal (EMTR) in locating the position of faults such as phase-to-ground shunt connections in power grids. EMTR directly transposes the idea of focusing energy back to its source introduced in original time-reversal (TR) methods. The current interpretation of EMTR, based on metrics measuring energy or peak-amplitude of focusing, is shown to suffer from ambiguities that increase the risk of inaccurate fault location. After pointing out under what conditions TR focusing occurs, an original frequency-domain reformulation of EMTR is introduced, showing that EMTR should more accurately be interpreted as a correlation estimator. New metrics based on this observation are introduced, taking into account the inhomogeneous transmission of electrical energy throughout complex networks, enabling a direct quantitative evaluation of the likelihood of locating a fault. Extensive numerical simulations confirm that the proposed formulation systematically improves the reliability of EMTR location estimates when faults occur in power grids of realistic complexity, highlighting the accrued risk that comes with the use of metrics that measure the scale of TR focusing rather than its quality.Keywords
Funding Information
- National Natural Science Foundation of China (51677148)
This publication has 21 references indexed in Scilit:
- Time-Reversed Excitation of Reverberation Chambers: Improving Efficiency and Reliability in the Generation of Radiated StressIEEE Transactions on Electromagnetic Compatibility, 2016
- Statistics of the performance of time reversal in a lossy reverberating mediumPhysical Review E, 2009
- Taking Advantage of Multiple Scattering to Communicate with Time-Reversal AntennasPhysical Review Letters, 2003
- Random multiple scattering of ultrasound. II. Is time reversal a self-averaging process?Physical Review E, 2001
- Time-reversed acousticsReports on Progress in Physics, 2000
- One-channel time-reversal in chaotic cavities: Theoretical limitsThe Journal of the Acoustical Society of America, 1999
- Accurate fault location technique for distribution system using fault-generated high-frequency transient voltage signalsIEE Proceedings - Generation, Transmission and Distribution, 1999
- Robust Acoustic Time Reversal with High-Order Multiple ScatteringPhysical Review Letters, 1995
- Maximum likelihood estimation of fault location on transmission lines using travelling wavesIEEE Transactions on Power Delivery, 1994
- Surge propagation on Japanese 500 kV untransposed transmission lineProceedings of the Institution of Electrical Engineers, 1974