Do time‐averaged, whole‐building, effective volatile organic compound ( VOC ) emissions depend on the air exchange rate? A statistical analysis of trends for 46 VOC s in U . S . offices
Authors:
- 15 June 2015
- journal article
- Published by Hindawi Limited in Indoor Air
- Vol. 26 (4) , 642-659
Abstract
We used existing data to develop distributions of time-averaged air exchange rates (AER), whole-building 'effective' emission rates of volatile organic compounds (VOC), and other variables for use in Monte Carlo analyses of U.S. offices. With these, we explored whether long-term VOC emission rates were related to the AER over the sector, as has been observed in the short term for some VOCs in single buildings. We fit and compared two statistical models to the data. In the independent emissions model (IEM), emissions were unaffected by other variables, while in the dependent emissions model (DEM), emissions responded to the AER via coupling through a conceptual boundary layer between the air and a lumped emission source. For 20 of 46 VOCs, the DEM was preferable to the IEM and emission rates, though variable, were higher in buildings with higher AERs. Most oxygenated VOCs and some alkanes were well fit by the DEM, while nearly all aromatics and halocarbons were independent. Trends by vapor pressure suggested multiple mechanisms could be involved. The factors of temperature, relative humidity, and building age were almost never associated with effective emission rates. Our findings suggest that effective emissions in real commercial buildings will be difficult to predict from deterministic experiments or models.Keywords
Funding Information
- National Science Foundation (1055584)
This publication has 75 references indexed in Scilit:
- A Method to Estimate the Chronic Health Impact of Air Pollutants in U.S. ResidencesEnvironmental Health Perspectives, 2012
- Experimental setup and analytical methods for the non-invasive determination of volatile organic compounds, formaldehyde and NO in exhaled human breathAnalytica Chimica Acta, 2010
- Reactions of ozone with human skin lipids: Sources of carbonyls, dicarbonyls, and hydroxycarbonyls in indoor airProceedings of the National Academy of Sciences, 2010
- Formaldehyde in the Indoor EnvironmentChemical Reviews, 2010
- Indoor secondary pollutants from cleaning product and air freshener use in the presence of ozoneAtmospheric Environment, 2006
- Sorption of organic gases in a furnished roomAtmospheric Environment, 2004
- Effect of outside air ventilation rate on volatile organic compound concentrations in a call centerAtmospheric Environment, 2003
- Characteristics and correlations of VOC emissions from building materialsInternational Journal of Heat and Mass Transfer, 2003
- Emissions of volatile organic compounds from building materials and consumer productsAtmospheric Environment (1967), 1987
- The effects of reduced ventilation on indoor air quality in an office buildingAtmospheric Environment (1967), 1983