Abstract
Grounding is essential to build effective lightning protection design for electric power equipment. The main role of grounding is to disperse abnormal current such as that from lightning into the soil via a grounding electrode. When the lightning current flows into the grounding electrode, the electrical potential of the electrode rises, and overvoltage arises between the equipment connected to the grounding electrode and nearby equipment. The overvoltage causes equipment to breakdown or malfunction. An effective grounding electrode controls the overvoltage at the equipment in a lightning strike and can ensure the normal operation of electrical equipment. The most common grounding electrodes are the vertical grounding rod and the horizontal buried electrode. A property of these grounding electrodes, known as effective length, has been investigated by many researchers. Many formulas to express effective length have already been proposed, all of which are determined heuristically on the basis of formulas that approximate the property from experimental or analytical test results; they are not formulas derived based on the physical phenomenon of grounding. In this paper, we first report on the results of the derivation of a formula for effective length based on the propagation velocity within the soil and the depth of penetration of the lightning surge into the soil. The aforementioned formula still has unknown constants. To decide those parameters, the finite-difference time-domain method is utilized.Keywords
This publication has 13 references indexed in Scilit:
- Impedance characteristics of grounding electrodes on earth surfaceElectric Power Systems Research, 2012
- Analytical Surveys of Transient and Frequency-Dependent Grounding Characteristics of a Wind Turbine Generator System on the Basis of Field TestsIEEE Transactions on Power Delivery, 2010
- A Study on Effective Length of Long Grounding Conductor in WindfarmIEEJ Transactions on Power and Energy, 2009
- Impulse Efficiency of Ground ElectrodesIEEE Transactions on Power Delivery, 2008
- Effective Length Consideration with the Minimize Per-Unit Length Impulse Impedance MethodIEEJ Transactions on Power and Energy, 2008
- Nonuniform Characteristics of a Horizontal Grounding ElectrodeIEEE Transactions on Power Delivery, 2007
- Effective Length of Counterpoise Wire Under Lightning CurrentIEEE Transactions on Power Delivery, 2005
- Verifying the Computational Method of Transient Performance with Respect to Grounding Systems based on the FD-TD Method.IEEJ Transactions on Power and Energy, 2003
- Conformal finite-different time-domain (FDTD) with overlapping gridsIEEE Transactions on Antennas and Propagation, 1992
- Impulse Impedance of Grounding GridsIEEE Transactions on Power Apparatus and Systems, 1980