Abstract
To solve the start‐up inrush current existing in the three‐phase grid‐connected inverter, a soft‐start control strategy for the three‐phase grid‐connected inverter with LCL filter is proposed. The analysis of start‐up inrush current is illustrated in detail. The capacitor current of the LCL filter is used to detect the closure of the grid‐connected switch, so the closing time of the grid‐connected switch does not need to be known. The detailed procedure and flowchart of the proposed soft‐start control method are provided. Finally, experimental results of a LCL‐type three‐phase grid‐connected inverter verify the theoretical analysis. The control strategy is easy to implement. The start‐up inrush current does not exist in the grid‐connected inverter.