Abstract
During 1993, 7 different samples taken at Reactor Outfall K-018 for Total Residual Chlorine exceeded the permitted requirement for the outfall of < 0.1 mg/L. Following the second exceedance, a Mitigation Action Plan was issued to investigate and identify the cause of the exceedances. The following potential causes were identified: (1) unauthorized/unknown operational discharge; (2) upstream industrial discharge to the Savannah River prior to SRS usage; (3) sanitary waste treatment plant discharge; (4) sampling methodology; (5) naturally occurring river water interference. Of these possibilities, it was determined that naturally occurring river water interference was the most likely cause and an in-depth sampling program, outlined in a Program Action Plan, was initiated to complete the investigation. The investigation determined that oxidized manganese present in the river water prior to usage within K-Area causes a false high reading for Total Residual Chlorine. It is this presence of the manganese interference, not operational discharge, that caused the exceedances at Outfall K-018.
Funding Information
  • USDOE, Washington, DC (United States)
  • DOE (AC09-89SR18035)