Online Cable Insulation Condition Evaluation Using Harmonic Measurement Data
- 17 June 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-13
Abstract
The existing online cable insulation condition (CIC) evaluation methods are mainly based on the insulation defects signals inside the cable, such as DC signals, or the transient disturbances from outside, such as ground faults. However, the former are usually weak and susceptible to environments, and the latter are not frequently obtainable. On the contrary, the steady-state disturbances, such as harmonics, which carry CIC information, have been widely measured and are readily available. Therefore, it is very convenient if we can use these data to evaluate CIC. In fact, based on the harmonic measurements at one end of a cable and the cable parameters corresponding to any CIC, the theoretical harmonic amplification factor (HAF) can be obtained, and the HAF is the ratio of harmonic values at both ends. In other words, if there is a deviation between the measured and theoretical HAF, it means that CIC has changed. Given this, we propose a novel method to evaluate CIC by minimizing the deviation, which includes three steps: 1) derive the theoretical HAF by using the cable parameters and harmonic measurements at one end of a cable, 2) construct the objective function to minimize the deviation and 3) solve the function to evaluate CIC by employing the Gauss-Newton iteration algorithm. The performance and effectiveness of the proposed method are verified through the simulation and field cases.Keywords
Funding Information
- National Natural Science Foundation of China (52277113)
- Natural Science Foundation of Sichuan Province (2023NSFSC0299)
This publication has 33 references indexed in Scilit:
- A review on partial discharge diagnosis in cables: Theory, techniques, and trendsMeasurement, 2023
- Identification of XLPE cable insulation defects based on deep learningGlobal Energy Interconnection, 2023
- Transient Disturbances Based Non-Intrusive Ageing Condition Assessment for Cross-Bonded CablesIEEE Access, 2020
- Study on the Quantitative Relationship Between Harmonic Amplification and Cable LengthIEEE Access, 2020
- Harmonic transmission characteristics for ultra-long distance AC transmission lines based on frequency-length factorElectric Power Systems Research, 2020
- Effect of thermal ageing on charge dynamics and material properties of 320 kV HVDC XLPEIEEE Transactions on Dielectrics and Electrical Insulation, 2019
- Evaluation of voltage endurance characteristics for new and aged XLPE cable insulation by electrical treeing testIEEE Transactions on Dielectrics and Electrical Insulation, 2019
- Online Partial Discharge Insulation Condition Monitoring of Complete High-Voltage NetworksIEEE Transactions on Industry Applications, 2018
- Evaluation of relationship between residual charge signal and AC breakdown strength of water-tree degraded 22 to 77 kV classes XLPE cables removed from service using pulsed voltagesIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Dielectric spectroscopy as a condition monitoring technique for cable insulation based on crosslinked polyethylenePolymer Testing, 2015