Abstract
A study on plug-in electric vehicle (PEV) charging load and its impacts on distribution transformers loss-of-life, is presented in this paper. The assessment is based on residential PEV battery charging. As the exact forecasting of the charging load is not possible, the method for predicting the electric vehicle (EV) charging load is stochastically formulated. With the help of the stochastic model, the effect of fixed, time of use, and real-time charging rates on the charging load and the resultant impact on transformer derating is investigated. A 38-bus test system is adopted as the test system including industrial harmonic sources. Test results demonstrate that uncontrolled EV charging might causes a noticeable change in the K-factor of the transformer, emerging the need for derating, while applying real-time rates for battery charging loads conquers this problem even in case of harmonic-rich chargers.Keywords
This publication has 13 references indexed in Scilit:
- Modelling the impacts of electric vehicle recharging on the Western Australian electricity supply systemEnergy Policy, 2011
- Load management in smart grids considering harmonic distortion and transformer derating2010
- The Impact of Charging Plug-In Hybrid Electric Vehicles on a Residential Distribution GridIEEE Transactions on Power Systems, 2009
- U.S. Department of Energy Vehicle Technologies Program -- Advanced Vehicle Testing Activity -- Plug-in Hybrid Electric Vehicle Charging Infrastructure Review2008
- Backward/Forward Sweep-Based Harmonic Analysis Method for Distribution SystemsIEEE Transactions on Power Delivery, 2007
- Measured transformer derating and comparison with harmonic loss factor (F/sub HL/) approachIEEE Transactions on Power Delivery, 2000
- Measurement of eddy-current loss coefficient P/sub EC-R/, derating of single-phase transformers, and comparison with K-factor approachIEEE Transactions on Power Delivery, 2000
- Transformer derating for harmonic currents: a wide-band measurement approach for energized transformersIEEE Transactions on Industry Applications, 1999
- A statistical method for predicting the net harmonic currents generated by a concentration of electric vehicle battery chargersIEEE Transactions on Power Delivery, 1997
- A procedure for derating a substation transformer in the presence of widespread electric vehicle battery chargingIEEE Transactions on Power Delivery, 1997