Simultaneous Determination of Dissolved Gases and Moisture in Mineral Insulating Oils by Static Headspace Gas Chromatography with Helium Photoionization Pulsed Discharge Detection
Authors:
- 19 June 2001
- journal article
- research article
- Published by American Chemical Society (ACS) in Analytical Chemistry
- Vol. 73 (14) , 3382-3391
Abstract
This paper presents the development of a static headspace capillary gas chromatographic method (HS-GC) for simultaneously determining dissolved gases (H2, O2, N2, CO, CO2, CH4, C2H6, C2H4, C2H2, C3H8) and moisture from a unique 15-mL mineral oil sample. A headspace sampler device is used to equilibrate the sample species in a two-phase system under controlled temperature and agitation conditions. A portion of the equilibrated species is then automatically split-injected into two chromatographic channels mounted on the same GC for their separation. The hydrocarbons and the lighter gases are separated on the first channel by a GS-Q column coupled with a MolSieve 5-Å column via a bypass valve, while the moisture is separated on the second channel using a Stabilwax column. The analytes are detected by using two universal pulsed-discharge helium ionization detectors (PDHID). The performance of the method was established using equilibrated vials containing known amounts of gas mixture, water, and blank oil. The signal is linear over the concentration ranges normally found for samples collected from open-breathing power transformers. Determination sensitivity varies with the nature of the species considered with values as high as 21 500 A × 10-9 s (μg/g)-1 for H2O, 46−216 A × 10-9 s (μL/L)-1 for the hydrocarbons and carbon oxides, and as low as 8−21 A × 10-9 s (μL/L)-1 for the O2 and N2 permanent gases. The detection limit of the method is between 0.08 and 6 μL/L for the dissolved gases, except for O2, N2, and CO2, where higher values are observed due to air intrusion during sampler operations, and 0.1 μg/g for the dissolved water. Ten consecutive measurements in the low and high levels of the calibration curves have shown a precision better than 12% and 6%, respectively, in all cases. A comparison study between the HS-GC method and the ASTM standard procedures on 31 field samples showed a very good agreement of the results. The advantages of configuring the arrangement with two PDHID over the conventional flame ionization and thermal conductivity detectors were clearly demonstrated.Keywords
This publication has 9 references indexed in Scilit:
- Bias Assessment of Current Technologies Used for the Determination of Low Levels of Moisture in Mineral Oil SamplesAnalytical Chemistry, 2001
- Determination of Water in NIST Reference Material for Mineral OilsAnalytical Chemistry, 2000
- Certification by the Karl Fischer method of the water content in SRM 2890, Water Saturated 1-Octanol, and the analysis of associated interlaboratory bias in the measurement processAnalytical and Bioanalytical Chemistry, 2000
- Determination of the Analytical Performance of a Headspace Capillary Gas Chromatographic Technique and Karl Fischer Coulometric Titration by System Calibration Using Oil Samples Containing Known Amounts of MoistureAnalytical Chemistry, 1999
- Decomposition of transformer oils: a new approach for the determination of dissolved gasesIEEE Transactions on Power Delivery, 1997
- Relative responses of various classes of compounds using a pulsed discharge helium photoionization detector experimental determination and theoretical calculationsJournal of Chromatography A, 1996
- Determination of dissolved gases and furan-related compounds in transformer insulating oils in a single chromatographic run by headspace/ capillary gas chromatographyJournal of Chromatography A, 1993
- Static headspace gas chromatographic determination of fault gases dissolved in transformer insulating oilsJournal of Chromatography A, 1993
- Determination of partition coefficients by automatic equilibrium headspace gas chromatography by vapor phase calibrationChromatographia, 1992