Understanding partial discharge activity in GIS due to particle movement under high frequency AC voltage adopting UHF technique
Authors:
- 1 August 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 21647011,p. 93-97
Abstract
Experimental studies were carried out to understand the partial discharges initiated due to particle movement in GIS operated at different pressure, under high frequency AC voltages adopting UHF technique. The rise time of partial discharge current pulse formed due to particle movement is 2ns. It is observed that the frequency contents of the signal radiated due to partial discharges generated due to particle movement in the electrode gap filled with SF6 lies in the UHF signal range, with its dominant frequency at near 1 GHz, irrespective of frequency of the supply voltage and the operating pressure. The UHF signal magnitude and the time required for 100 UHF signal to form shows direct correlation. Ternary diagram clearly indicates that irrespective of frequency of the supply voltage, the UHF signal location (signal generated due to PD) in the ternary diagram is the same.Keywords
This publication has 8 references indexed in Scilit:
- A review of faults detectable by gas-in-oil analysis in transformersIEEE Electrical Insulation Magazine, 2002
- Factors affecting the dynamics of wire particles in gas-insulated systemsEuropean Transactions on Electrical Power, 2001
- Dynamics of metallic particle contaminants in GIS with dielectric-coated electrodesIEEE Transactions on Power Delivery, 2000
- A pulsed GTEM system for UHF sensor calibrationIEEE Transactions on Instrumentation and Measurement, 1998
- The excitation of UHF signals by partial discharges in GISIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- Partial discharge. XIII. Acoustic partial discharge detection-fundamental considerationsIEEE Electrical Insulation Magazine, 1992
- Partial discharge. X. PD in gas-insulated substations-measurement and practical considerationsIEEE Electrical Insulation Magazine, 1992
- Time dependence of AC flashover characteristics for particle-initiated breakdown in GISIEEE Transactions on Power Delivery, 1989