Abstract
This paper presents the application of a methodology for estimating the inertia of generator groups of the Brazilian Interconnected Power System (BIPS) using phasor measurement unit (PMU) data acquired at 230 kV transmission substations. The methodology has been applied using synchrophasor data collected during disturbances in a Brazilian subsystem with two hydroelectric power plants (HPPs), as well as two interconnections with the rest of the BIPS, composed of three 230 kV transmission lines and a back-to-back converter station. Simulated and real data have been analyzed to assess the limitations and to identify required improvements toward a practical application of the perturbation-based methodology in the estimation of the inertia of real systems. A by-product of the application of the methodology is the obtaining of a second-order dynamic equivalent, useful for model-based online applications.
Funding Information
  • Coordination for the Improvement of Higher Education Personnel (CAPES) and developed for the State Grid Brazil Holding (SGBH) Special Protection Scheme (SEP) Project (code PD-10307-0221/2022)
  • National Electric Energy Agency (ANEEL) R&D program
  • Research and Innovation Support Foundation of Santa Catarina State
  • National Council for Scientific and Technological Development (CNPq) and Institute of Systems Engineering and Computers Technology and Science of Brazil