Numerical simulation of the CO2 diffusion effect on low turbulent mixed convection in a ventilated room heated by the bottom
Authors:
Open Access
- 1 January 2021
- journal article
- research article
- Published by National Library of Serbia in Thermal Science
- Vol. 25 (6 Part B) , 4783-4796
Abstract
A double-diffusive mixed convection within low-turbulent regime in a ventilated cavities filled with an air-CO2 mixture and heated from below has been numerically investigated. The lower wall was sustained at a uniform temperature and CO2-concentration. The vertical and upper walls were kept at external temperature and CO2-concentration. To analyze the behavior of flow, the ventilation effectiveness for temperature distribution and removal of CO2-contaminant, four configurations were dealt. These differ from each other by the location of the mixture inlet and outlet gaps. Likewise, three CO2-concentrations were considered (103, 2x103 and 3x103 ppm) to investigate the influence of the CO2-diffusion on the ventilation effectiveness. The numerical simulations were performed by considering closed Reynolds averaged-Navier-Stokes (RANS) equations using the Re-Normalization Group k-ε model. The governing equations' set was then solved using the finite volume method, in which the pressure-velocity coupling was handled using the SIMPLEC algorithm. Validation of the numerical model was achieved by comparing our results with available experimental data. The obtained results indicate that the CO2-diffusion effect on the air movement and the ventilation effectiveness for temperature distribution can be neglected in the present study. However, the CO2-diffusion remains a key parameter in terms of indoor air quality index. Also, it was found that one of the studied configurations provides a better ventilation effectiveness to remove heat and CO2-contaminant, and insures a homogeneous temperature and CO2-concentration in the occupied zone. The three other configurations maintain an acceptable level of heat and can be used in temperate climate to ensure good indoor air quality.Keywords
This publication has 20 references indexed in Scilit:
- Influence of air change rates on indoor CO 2 stratification in terms of Richardson number and vorticityBuilding and Environment, 2018
- Numerical investigation of transient heat and mass transfer by natural convection in a ventilated cavity: Outlet air gap located close to heat sourceInternational Journal of Heat and Mass Transfer, 2014
- A review of the performance of different ventilation and airflow distribution systems in buildingsBuilding and Environment, 2014
- Optimum ventilation based on the ventilation effectiveness for temperature and CO2 distribution in ventilated cavitiesInternational Journal of Heat and Mass Transfer, 2013
- Influence of turbulent boundary conditions on RANS simulations of pollutant dispersion in mechanically ventilated enclosures with transitional slot Reynolds numberBuilding and Environment, 2013
- Air distribution and ventilation effectiveness in an occupied room heated by warm airEnergy and Buildings, 2012
- Indoor air quality assessment in child care and medical facilities in KoreaEnvironmental Monitoring and Assessment, 2011
- Effect of a contaminant source (CO2) on the air quality in a ventilated roomEnergy, 2011
- Aldehyde measurements in indoor environments in Strasbourg (France)Atmospheric Environment, 2006
- Fluid, heat and contaminant transport structures of laminar double-diffusive mixed convection in a two-dimensional ventilated enclosureInternational Journal of Heat and Mass Transfer, 2004