Induced Losses in Three-Core SL-Type High-Voltage Cables
- 13 November 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (3) , 1505-1513
Abstract
It is considered that the present IEC 60287 standard overestimates the induced losses in SL-type armored cables, which are commonly used to connect offshore windfarms to the onshore grid. This paper addresses the issue through a series of equivalent-circuit models for the estimation of circulating-current, eddy-current, and armor losses in these cables. Finite-element models are used for further validation. Both the finite-element and the equivalent-circuit models use an equivalent-material representation of the armor layer, for which two calculation methods are developed. The results demonstrate clearly that the equation for armor loss in such cables as presently used in IEC standards is overly conservative.Keywords
This publication has 1 reference indexed in Scilit:
- Circulating current and hysteresis lossesin screens,sheaths and armour of electric power cables — mathematicalmodels and comparison with IEC Standard 287IEE Proceedings - Science, Measurement and Technology, 1997