Faulted Line-Section Location in Distribution System With Inverter-Interfaced DGs Using Sparse Meters
- 27 June 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 14 (1) , 413-423
Abstract
This paper proposes a faulted line-section location method using sparse meters for the distribution networks (DNs) with high penetration of inverter interfaced distributed generations (IIDGs). By modeling the IIDGs as equivalent impedances instead of current sources, the fault component model of the DN with IIDGs can be transferred from a multi-current feeding system towards the sole-current feeding system. On this basis, the Bayesian Compressed Sensing (BCS) algorithm is applied to achieve the sparse solution of the fault current to indicate the faulted line-section. Moreover, to reduce the required meters for monitoring the IIDGs, a node partition scheme is designed based on the analysis of IIDG with different control strategies. The proposed fault location method requires only 15 meters for an IEEE 69-node distribution network with 20 IIDGs. Simulation results show that the location success rate is beyond 95% for various fault scenarios which is a 55% improvement over the existing BCS-based method.Keywords
Funding Information
- National Natural Science Foundation of China (51777071, 51725702, 52061635102)
This publication has 32 references indexed in Scilit:
- High Frequency Impedance Based Fault Location in Distribution System With DGsIEEE Transactions on Smart Grid, 2016
- Fault Detection and Faulted Line Identification in Active Distribution Networks Using Synchrophasors-Based Real-Time State EstimationIEEE Transactions on Power Delivery, 2016
- Fault Location Using Wide-Area Measurements and Sparse EstimationIEEE Transactions on Power Systems, 2015
- A Novel Method for Single and Simultaneous Fault Location in Distribution NetworksIEEE Transactions on Power Systems, 2014
- Fault-Location Scheme for Power Distribution System with Distributed GenerationIEEE Transactions on Power Delivery, 2014
- Power Controllability of a Three-Phase Converter With an Unbalanced AC SourceIEEE Transactions on Power Electronics, 2014
- Power Quality Event Classification Under Noisy Conditions Using EMD-Based De-Noising TechniquesIEEE Transactions on Industrial Informatics, 2013
- Sparse Solutions of Underdetermined Systems2013
- HIL Evaluation of Power Flow Control Strategies for Energy Storage Connected to Smart Grid Under Unbalanced ConditionsIEEE Transactions on Power Electronics, 2012
- PMU-Based Fault Location Using Voltage Measurements in Large Transmission NetworksIEEE Transactions on Power Delivery, 2012