Distribution Surge Arrester Behavior Due to Lightning Induced Voltages
Author:
- 1 January 1986
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 1 (1) , 171-178
Abstract
Using a calculation program for the analysis of lightning induced voltages on a multi-conductor system, the protection effects of surge arresters on three-phase distribution lines were studied. Installation of surge arresters every 200 meters provides a 6.6 kV distribution line with good protection effects. Even severe lightning induced voltage will not create large arrester discharging currents.Keywords
This publication has 3 references indexed in Scilit:
- Calculation of Lightning-Induced Voltages on Overhead Multiconductor SystemsIEEE Transactions on Power Apparatus and Systems, 1984
- Lighting - Induced Overvoltages on Overhead Distribution LinesIEEE Transactions on Power Apparatus and Systems, 1982
- Frequency of distribution arrester discharge currents due to direct strokesIEEE Transactions on Power Apparatus and Systems, 1976