New approach to improve sensitivity of differential and restricted earth fault protections for industrial transformers
Open Access
- 1 April 2016
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (6) , 1486-1494
Abstract
Differential relays are the main protection for power transformers including transmission and industrial transformers. Protection against internal fault is generally relegated to these relays. The most probable internal fault of the industrial transformer is phase to ground type. To limit the fault current in this condition, a limiter resistor is utilised in the transformer. However, it has considerable impact on sensitivity of the differential and restricted earth fault (REF) protections. In this study, an effective approach is proposed to improve the differential and REF protections sensitivity of the industrial transformers. The proposed technique not only realises the fault current limitation function, but preserves sensitivity of the protections. In this method, a developed fault current limiter is utilised in the transformer neutral instead of the neutral grounding resistor. The performance of the proposed technique is evaluated by some simulations and experiments. The results confirm the high capability of the proposed technique in different conditions.Keywords
This publication has 16 references indexed in Scilit:
- Power transformer protection based on decision tree approachIET Electric Power Applications, 2014
- Development of a high‐performance bridge‐type fault current limiterIET Generation, Transmission & Distribution, 2014
- Self‐adaptive transformer differential protectionIET Generation, Transmission & Distribution, 2013
- Extended Park's vector approach-based differential protection of three-phase power transformersIET Electric Power Applications, 2012
- Development of an Efficient Solid-State Fault Current Limiter for MicrogridIEEE Transactions on Power Delivery, 2012
- Differential protection for power transformers with non-standard phase shifts2011
- Probabilistic neural-network-based protection of power transformerIET Electric Power Applications, 2007
- Protection and Commissioning of Multifunction Digital Transformer Relays at Medium Voltage Industrial FacilitiesIEEE Transactions on Industry Applications, 2005
- Superconducting FCL: Design and ApplicationIEEE Transactions on Applied Superconductivity, 2004
- Design of 6.6 kV, 100 A saturated DC reactor type superconducting fault current limiterIEEE Transactions on Applied Superconductivity, 2003