Optimizing cooling setpoint using adaptive thermal comfort concept for school building in desert climates under current and future climates
- 1 November 2024
- journal article
- research article
- Published by Emerald Publishing in Smart and Sustainable Built Environment
- Vol. 14 (7) , 2048-2068
Abstract
Purpose: This paper aims to compare the impacts of adaptive daily and seasonal cooling setpoints on cooling energy consumption and overheating hours to determine which approach is more effective in a desert climate, develop a methodology that effectively integrates passive strategies with adaptive daily and seasonal cooling setpoint strategies and assess how future climate conditions will impact these strategies in the medium and long term. Design/methodology/approach: (1) Integrate adaptive thermal comfort principles into mechanical cooling systems to find the optimized cooling setpoint. (2) Evaluating the optimized cooling setpoints using a mixed-mode operation: In this step, the natural ventilation is activated by opening 40% of the window area when the indoor temperature is higher than 23°C and the outdoor temperature. Both the adaptive seasonal and daily setpoint strategies are evaluated. (3) If overheating hours exceed acceptable limits gradually add mitigation measures (e.g. exterior shading, cool roofs and green roofs). (4) If necessary, further reduce the cooling setpoint until acceptable limits are met. (5) Generate extreme future climate scenarios and evaluate the optimized model. (6) Implement additional measures and setpoint adjustments to maintain acceptable overheating hours in future conditions. Findings: Although the building complies with the Dubai Green Code and uses external shading, its cooling energy consumption was 92 kWh/m² in 2021 with a 24°C setpoint. Using the adaptive seasonal setpoint combined with a cool roof, night cooling and cross-ventilation reduces cooling energy consumption by 52, 48 and 35% in 2020, 2050 and 2090, respectively, with overheating hours not exceeding 40 h annually. Using an adaptive daily setpoint strategy with the same mitigation measures is similarly effective; it achieved a 57, 42 and 34% reduction in cooling energy consumption in 2020, 2050 and 2090, respectively, while eliminating overheating hours. Originality/value: The originality and value of this study lie in optimizing cooling setpoints without the effect of overheating hours in desert climates. Using the adaptive seasonal setpoint combined with a cool roof, night cooling and cross-ventilation reduces cooling energy consumption by 52, 48 and 35% in 2020, 2050 and 2090, respectively, with overheating hours not exceeding 40 h annually. Using an adaptive daily setpoint strategy with the same mitigation measures is similarly effective; it achieved a 57, 42 and 34% reduction in cooling energy consumption in 2020, 2050 and 2090, respectively, while eliminating overheating hours. Highlights:Keywords
This publication has 68 references indexed in Scilit:
- Assessing the energy saving potential of using adaptive setpoint temperatures: The case study of a regional adaptive comfort model for Brazil in both the present and the futureBuilding Simulation, 2023
- An investigation of shading devices in a hot region: A case study in a school buildingAin Shams Engineering Journal, 2021
- A comparative study of thermal comfort in learning spaces using three different ventilation strategies on a tropical university campusBuilding and Environment, 2019
- Thermal comfort study in naturally ventilated school classrooms in composite climate of IndiaBuilding and Environment, 2018
- Strongly increasing heat extremes in the Middle East and North Africa (MENA) in the 21st centuryClimatic Change, 2016
- Energy conservation in museums using different setpoint strategies: A case study for a state-of-the-art museum using building simulationsApplied Energy, 2015
- Evaluating the sustainability impact of improved building insulation: A case study in the Dubai residential built environmentBuilding and Environment, 2013
- Providing better thermal and air quality conditions in school classrooms would be cost-effectiveBuilding and Environment, 2013
- Linking occupants’ thermal perception and building thermal performance in naturally ventilated school buildingsApplied Energy, 2012
- Evaluating the potential impact of global warming on the UAE residential buildings – A contribution to reduce the CO2 emissionsBuilding and Environment, 2009