High Impedance Fault Detection Based on Arc Changing Tendency and Nonlinear Least Squares for Active Distribution Networks
- 18 March 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Informatics
- Vol. 20 (6) , 8572-8584
Abstract
When a high-impedance fault (HIF) occurs in active distribution networks, the features of the arc current are weak and can be easily confused with the features of the capacitor switching current or load switching current. Meanwhile, fault currents are easily affected by the harmonics and noises of distributed generators, which may result in low detection accuracy for existing HIF detection methods. To accurately detect high-impedance arc faults, an HIF detection method based on the arc changing tendency and nonlinear least squares (NLSs) are proposed. In the proposed method, variational mode decomposition and windowed fast Fourier transform are first employed to extract current amplitudes. Then, NLSs method is introduced to quantitatively estimate the changing tendency of the current amplitudes. Finally, an HIF detection criterion is developed based on the sign of the coefficient in the nonlinear function. Both simulation results and field test results confirm the effectiveness and applicability of the proposed HIF detection method. The inspiration for the proposed method is drawn from the physical characteristics during the initial stage of HIFs. These characteristics remain unaffected by network operation conditions. Comparative analysis reveals that the proposed method offers higher detection accuracy and reliability compared to existing conventional methods.Keywords
Funding Information
- National Natural Science Foundation of China (52177114, 61403127)
- Electric Power Research Institute
- State Grid Shanxi Electric Power Company (5226KY23001C)
This publication has 38 references indexed in Scilit:
- A Resilient Protection Scheme for Common Shunt Fault and High Impedance Fault in Distribution Lines Using Wavelet TransformIEEE Systems Journal, 2022
- LSTM Recurrent Neural Network Classifier for High Impedance Fault Detection in Solar PV Integrated Power SystemIEEE Access, 2021
- High impedance fault detection method based on the short‐time Fourier transformIET Generation, Transmission & Distribution, 2018
- Modified FFT based high impedance fault detection technique considering distribution non-linear loads: Simulation and experimental data analysisInternational Journal of Electrical Power & Energy Systems, 2018
- Variational mode decomposition denoising combined the detrended fluctuation analysisSignal Processing, 2016
- Parameter estimation for HFM signals using combined STFT and iteratively reweighted least squares linear fittingSignal Processing, 2014
- Time‐frequency transform‐based differential scheme for microgrid protectionIET Generation, Transmission & Distribution, 2014
- High Impedance Faults: From Field Tests to ModelingJournal of Control, Automation and Electrical Systems, 2013
- Detection of frauds and other non-technical losses in a power utility using Pearson coefficient, Bayesian networks and decision treesInternational Journal of Electrical Power & Energy Systems, 2012
- High impedance fault detection using combination of multi-layer perceptron neural networks based on multi-resolution morphological gradient features of current waveformIET Generation, Transmission & Distribution, 2011