Abstract
The paper describes some of the fault studies performed for the protection system of ENEL Distribuzione's experimental MV loop lines. The system consists of a pilot relaying scheme using directional overcurrent relays for ground and phase fault detection. With reference to an actual implementation (a MV distribution network including a loop line, in Southern Italy), attention is focused on phase fault detection, aiming at the determination of magnitude and phase angle settings for relays. The effects of fault location and fault resistance are investigated by detailed simulations, resulting in tentative phase relay settings for the new protection scheme.Keywords
This publication has 4 references indexed in Scilit:
- Ground Fault Protection in ENEL Distribuzione's Experimental MV Loop Line2014
- Schema project-innovative criteria for management and operation of a closed ring mv network2013
- Innovative protection system on distribution network2013
- Meshed vs. radial MV distribution network in presence of large amount of DG2004