Adequacy of air change rate as the sole indicator of an air distribution system's effectiveness to mitigate airborne infectious disease transmission caused by a cough release in the room with overhead mixing ventilation: A case study
Authors:
- 23 September 2013
- journal article
- research article
- Published by Taylor & Francis in HVAC&R Research
- Vol. 19 (8) , 947-961
Abstract
In indoor environments where airborne infectious disease transmission is of concern, air change rate is conventionally used as the sole indicator of air delivery system performance. This indicator, based on the total volume dilution reasoning, suggests that increase of the supply flow rate will reduce risk of airborne infectious disease transmission. Results obtained from recent studies on cough release conducted in the field environmental chamber (FEC) at the National University of Singapore indicate that increase of supply flow rate may cause increase in the airborne infection risk transmission for several positions of the cough source and the susceptible person in relation to the supply and return air grills. Particle image velocimetry (PIV) was used for airflow field investigation, while a Grimm 1.108 aerosol counter was used to measure droplet concentration in the FEC. Results from this study imply that a local airflow pattern is an important factor influencing dispersion of cough droplets and consequential exposure. It is demonstrated that increase in supply flow rate can lead to an increase in exposure under certain circumstances. This further implies that air change rate should not be used as the sole indicator of the air delivery system's ability to reduce exposure to airborne infectious droplets.Keywords
This publication has 40 references indexed in Scilit:
- Different Types of Door-Opening Motions as Contributing Factors to Containment Failures in Hospital Isolation RoomsPLOS ONE, 2013
- Influenza Virus Aerosols in Human Exhaled Breath: Particle Size, Culturability, and Effect of Surgical MasksPLOS Pathogens, 2013
- Particle Image Velocimetry of Human CoughAerosol Science and Technology, 2011
- Personalized ventilation as a control measure for airborne transmissible disease spreadJournal of The Royal Society Interface, 2009
- An Overview of Room Air Motion Measurement: Technology and ApplicationHVAC&R Research, 2007
- Modelling control measures to reduce the impact of pandemic influenza among schoolchildrenEpidemiology and Infection, 2007
- Protection of Occupants from Exhaled Infectious Agents and Floor Material Emissions in Rooms with Personalized and Underfloor VentilationHVAC&R Research, 2007
- Transport Characteristics of Expiratory Droplets and Droplet Nuclei in Indoor Environments With Different Ventilation Airflow PatternsJournal of Biomechanical Engineering, 2006
- Toward Understanding the Risk of Secondary Airborne Infection: Emission of Respirable PathogensJournal of Occupational and Environmental Hygiene, 2005
- Factors that make an infectious disease outbreak controllableProceedings of the National Academy of Sciences, 2004