Investigation and Improvement of Transient Response of DVR at Medium Voltage Level
Authors:
- Poh Chiang LohPLPoh Chiang Loh
- Frede BlaabjergFrede Blaabjerg
- D. Mahinda VilathgamuwaDVD. Mahinda Vilathgamuwa
- 24 September 2007
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 43 (5) , 1309-1319
Abstract
An area of interest for dynamic voltage restorer (DVR) research is the damping of transient oscillations initiated at the start and at the recovery instant from a voltage sag. Nonlinear loads, with harmonic currents close to the DVR filter resonance frequency, can also excite the resonance oscillations. To compensate voltage sags and dampen high-frequency oscillations simultaneously, an investigation of the transient response of DVR is first carried out. Possible control schemes and their effects on the oscillation attenuation are also studied. Such studied control schemes include the commonly used single voltage loop control, voltage feedback plus reference feedforward control, and double-loop control with an outer voltage loop and an inner current loop. Subsequently, an effective and simple resonance damping method is proposed by employing a closed-loop control with an embedded two-step Posicast controller. The proposed control methods have been extensively tested on a 10-kV DVR system. It is shown that the proposed damping methods improve both the transient and steady-state performance of the DVR.Keywords
This publication has 16 references indexed in Scilit:
- Microgrid Power Quality Enhancement Using a Three-Phase Four-Wire Grid-Interfacing CompensatorIEEE Transactions on Industry Applications, 2005
- A Dynamic Voltage Restorer (DVR) With Selective Harmonic Compensation at Medium Voltage LevelIEEE Transactions on Industry Applications, 2005
- Implementation and Test of an Online Embedded Grid Impedance Estimation Technique for PV InvertersIEEE Transactions on Industrial Electronics, 2005
- A Simple Method for Suppression of Resonance Oscillation in PWM Current Source ConverterIEEE Transactions on Power Electronics, 2005
- Multilevel Dynamic Voltage RestorerIEEE Power Electronics Letters, 2004
- Transient performance improvement of static series compensator by double vector control2004
- Control and Testing of a Dynamic Voltage Restorer (DVR) at Medium Voltage LevelIEEE Transactions on Power Electronics, 2004
- Digital control of a boost converter using Posicast2004
- Stationary frame current regulation of PWM inverters with zero steady-state errorIEEE Transactions on Power Electronics, 2003
- Feedback control with PosicastIEEE Transactions on Industrial Electronics, 2003