End-of-life and replacement strategies for RTV silicone rubber coatings
Authors:
- E. CherneyECE. Cherney
- A. El-HagA. El-Hag
- 20 February 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 21 (1) , 253-261
Abstract
The paper provides several methods to assess the condition of RTV coated porcelain/toughened glass insulators in the field. Visual observations of arcing and audible corona are the first indications that signal changes to the coating have taken place. It emphasizes that in the absence of reliable data one can use observations based on hydrophobicity to evaluate when maintenance or replacement of the coated insulators is necessary. Life extension strategies are suggested. It also demonstrates that there are differences in the hydrophobicity characteristics among commercially available coatings, and these can be quantified using standard laboratory techniques. Field experience suggests that the life of the RTV coatings can exceed 10 years even under the severest conditions of pollution.Keywords
This publication has 20 references indexed in Scilit:
- Evaluating station post insulator performance from electric field calculationsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Aging Characteristics of RTV Silicone Rubber Insulator CoatingsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Laboratory analysis of naturally aged silicone rubber polymer insulators from contaminated environments, 138 to 145 kV2002
- Field and laboratory aging of RTV silicone insulator coatingsIEEE Transactions on Power Delivery, 2000
- Hydrophobicity loss and recovery of silicone HV insulationIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Degradation of a silicone-based coating in a substation applicationIEEE Transactions on Power Delivery, 1999
- Chemical changes at the surface of RTV silicone rubber coatings on insulators during dry-band arcingIEEE Transactions on Dielectrics and Electrical Insulation, 1994
- Accelerated aging and flashover tests on 138 kV nonceramic line post insulatorsIEEE Transactions on Power Delivery, 1993
- Rain and contamination tests on HVDC wall bushings with and without RTV coatingsIEEE Transactions on Power Delivery, 1991
- Surface hydrophobicity of polymers used for outdoor insulationIEEE Transactions on Power Delivery, 1990