High Voltage Insulation Failure Mechanisms
Authors:
- 1 June 2008
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 1089084X,p. 162-165
Abstract
There are many statistics dealing with failure causes of high voltage rotating machines. While these statistics prove the relevance of the insulation as failure cause, they give little information on the real failure mechanism. This paper gives results of a research project which was launched to investigate degradation and final breakdown of the mica insulation in rotating machines. Final failure of the insulation is usually caused by electric breakdown through a tree channel. Formation and propagation of trees in the mica insulation therefore reflect the ageing process of the insulation. Dominating ageing factors of the mica insulation are thermal and mechanical stress. Manufacturing defects of the mica insulation - such as delaminations, cracks, voids and wrinkled or damaged mica layers - accelerate the formation and propagation of trees. Good workmanship and proper selection and application of the insulation materials are important factors for the lifetime of high voltage rotating machines.Keywords
This publication has 1 reference indexed in Scilit:
- A survey of faults on induction motors in offshore oil industry, petrochemical industry, gas terminals, and oil refineriesIEEE Transactions on Industry Applications, 1995