Hygrothermal assessment of internally insulated solid masonry walls fitted with exterior hydrophobization and deliberate thermal bridge
Abstract
Relative humidity (RH) and temperature were measured in several solid masonry walls with embedded wooden beams, fitted with autoclaved aerated concrete (AAC) thermal insulation on the interior surface and exposed to a cool, temperate climate. The field study was based on the use of a 40‐feet insulated reefer container reconfigured with eight 1 × 2 m holes containing the solid masonry walls. The study investigated the influence of AAC thermal insulation on the interior side with a combination of exterior hydrophobization and a deliberate thermal bridge in front of the embedded wooden wall plate using a material with higher thermal conductivity. Validated HAM simulations were used to investigate the effect of controlling the indoor humidity, and how this would affect the theoretical risk predictions from the damage models. Experimental findings indicate that hydrophobization of solid masonry walls with internal insulation have both positive and negative effects on the moisture balance of the wall, in relation to moisture‐induced damage, and that a deliberate thermal bridge installed in front of the embedded wooden wall plate can reduce the moisture content in the wooden elements. Simulation findings indicate that a combination of exterior hydrophobization and decreased indoor moisture load can reduce the RH to acceptable levels in relation to moisture induced damage at the interface between existing wall and new insulation. No major changes were observed in relation to the risk of frost damage at the exterior surface.Keywords
Funding Information
- Realdania
This publication has 11 references indexed in Scilit:
- Effect of façade impregnation on feasibility of capillary active thermal internal insulation for a historic dormitory – A hygrothermal simulation studyConstruction and Building Materials, 2016
- Internal insulation applied in heritage multi-storey buildings with wooden beams embedded in solid masonry brick façadesBuilding and Environment, 2016
- Mold Risk Classification Based on Comparative Evaluation of Two Established Growth ModelsEnergy Procedia, 2015
- Full-scale test of an old heritage multi-storey building undergoing energy retrofitting with focus on internal insulation and moistureBuilding and Environment, 2015
- Hygrothermal performance of internally insulated brick wall in cold climate: A case study in a historical school buildingJournal of Building Physics, 2014
- Investigation of interior post-insulated masonry walls with wooden beam endsJournal of Building Physics, 2012
- Towards modelling of decay risk of wooden materialsEuropean Journal of Wood and Wood Products, 2010
- Interior Insulation Retrofits of Load-Bearing Masonry Walls in Cold ClimatesJournal of Green Building, 2007
- A mathematical model of mould growth on wooden materialWood Science and Technology, 1999
- Effect of interior and exterior insulation on the hygrothermal behaviour of exposed wallsMaterials and Structures, 1998