Insulation characteristics of epoxy insulator with internal delamination-shaped micro-defects
Authors:
- 21 October 2013
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 20 (5) , 1851-1858
Abstract
The degradation characteristic of solid insulators is considered to be one of the key factors to perform a risk assessment of highly aged gas insulated switchgear (GIS). The present study experimentally obtained the insulation characteristics of epoxy insulator mainly with an internal microscopic delamination-shaped defect. In the experiment, a short-time breakdown electric field (EF) was initially obtained and comparison was made with the breakdown EF for the void and crack defects to evaluate the breakdown risk with respect to the defect shape. These defect models (delamination, void, and crack) were designed and produced so that an apparent partial (PD) might be 1 pC in an actual 550 kV-GIS spacer. Consequently, it emerged that the area where the EF was concentrated influenced the breakdown. Of the three types of defect, the degree of EF concentration was the lowest for delamination defects, meaning the lowest breakdown risk for the same. Subsequently, the V-t characteristics were obtained through an EF acceleration test. The V-t characteristics obtained were extrapolated to estimate the breakdown risk in 30 to 50 years operation, which is considered the design life of GIS. As a result, it was determined that the potential for eventual breakdown was extremely low under the normal operating EF, even if a delamination defect equivalent to an apparent PD of 1 pC was present in an actual 550 kV-GIS spacer. Hence, controlling a defect using 1 pC for actual GIS is considered to ensure reliability under long-term operation.Keywords
This publication has 13 references indexed in Scilit:
- Cross-equipment Evaluation of Partial Discharge Measurement and Diagnosis Techniques in Electric Power Apparatus for Transmission and DistributionIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Partial discharge characteristics leading to breakdown of GIS spacer samples with degraded insulation performance2004
- Investigation of electrical insulation diagnosis of solid insulators in GIS by partial discharge current pulse waveform analysis (PD-CPWA)2003
- V-t Characteristics of Gas Insulating Spacer Model for Sustained AC VoltageIEEJ Transactions on Power and Energy, 1997
- Measurement and simulation of PD in epoxy voidsIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- A generalized approach to partial discharge modelingIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- The importance of statistical characteristics of partial discharge dataIEEE Transactions on Electrical Insulation, 1992
- Formation of nitrides and pressure decrease in an enclosed void between metal electrode and epoxy resin.IEEJ Transactions on Fundamentals and Materials, 1987
- Tree growth in epoxy resin at the final stage of internal partial discharge degradation.IEEJ Transactions on Fundamentals and Materials, 1984
- The voltage endurance of cast epoxy resins1978