Novel Identification Method of Stator Single Phase-to-Ground Fault for Cable-Wound Generators
Authors:
- Qing TianQTQing Tian
- Pei LiuPLPei Liu
- 30 April 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 23 (2) , 349-357
Abstract
A new criterion to detect the stator single phase-to-ground fault for Powerformer is proposed in this paper, which is based on the direction of zero-sequence compositive power flow. By virtue of the analysis of new fault characteristics of Powerformer and the comparison with conventional methods, a novel identification scheme is put forward. The proposed approach detects the ground fault by analyzing the power direction. Only zero-sequence current from the terminal of Powerformer and zero-sequence voltage from the busbar are used in this scheme. Combined with third-harmonic principle, it can provide a 100% coverage of fault detection for the stator windings of Powerformer. The effectiveness of this scheme is validated with the Matlab simulation results.Keywords
This publication has 8 references indexed in Scilit:
- Studies on the Internal Fault Simulations of a High-Voltage Cable-Wound GeneratorIEEE Transactions on Energy Conversion, 2007
- Suppression of slot discharges in a cable wound generatorIEEE Transactions on Energy Conversion, 2003
- Improvement of subharmonic injection schemes for huge hydro-generator stator ground fault protection2003
- Utilizing third harmonic 100% stator ground fault protection, a cogeneration experience2002
- Powerformer/sup TM/-experiences from the application of extruded solid dielectric cables in the stator winding of rotating machines2002
- A new power-based digital algorithm for generator protectionIEEE Power Engineering Review, 2000
- Powerformer(R): a giant step in power plant engineering1999
- The heart of a new machineIEE Review, 1998