A method for predicting key data center temperatures by known airflow streams
Authors:
- 1 May 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 10879870,p. 1202-1208
Abstract
We present a simplified model for predicting key data-center temperatures, such as those of rack inlets and cooler returns. If the primary airflow streams into and out of all racks and coolers are known, these airflow values can be combined with the assumption of a well-mixed room ambient volume to create a simplified, but energy-balanced, set of temperature equations. Since the temperature estimates are restricted to only a small number of data center objects, solutions can be found quickly. This temperature model can be adapted to quickly address data center design or management issues without multiple Computational Fluid Dynamics (CFD) simulations. Optimized cooler set points can be quickly found with only slight adjustments to the model. In another application, the effects of cooler capacity models are easily understood when incorporated within the temperature model. The object-averaged inlet temperature estimates generated by this temperature model compare favorably to those found by CFD.Keywords
This publication has 12 references indexed in Scilit:
- Potential-Flow Modeling for Data Center Applications2011
- The Effect of Under-Floor Obstructions on Data Center Perforated Tile Airflow2011
- From Chip to Cooling Tower Data Center Modeling: Chip Leakage Power and its Impact on Cooling Infrastructure Energy Efficiency2011
- Energy Modeling of Air-Cooled Data Centers: Part II—The Effect of Recirculation on the Energy Optimization of Open-Aisle, Air-Cooled Data Centers2011
- Data center air management metrics-practical approach2010
- Measurement-based modeling for data centers2010
- Thermal zones for more efficient data center energy management2010
- A Real-Time Data Center Airflow and Energy Assessment Tool2009
- A Flow-Network Model for Predicting Rack Cooling in Containment Systems2009
- Partially Decoupled Aisle Method for Estimating Rack-Cooling Performance in Near-Real Time2007