Fault behavior of wind farms with fixed-speed and Doubly-Fed Induction Generators
Authors:
- 1 June 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-7
Abstract
This paper focuses on the fault current contribution of wind farms with Fixed-Speed (FSIG) and Doubly-Fed Induction Generators (DFIG). The fault current delivered by a single FSIG during both symmetrical and unsymmetrical faults is found analytically and validated through simulations. Simulations of a detailed model of a wind farm with several FSIG or DFIG are then performed to investigate the total fault current contribution at the Point of Common Coupling. The scope is to check the validity of a single-machine approach to predict the fault contribution of the wind farm. It has been found that both in the case of FSIG and DFIG wind farms, the single-machine approach is reasonable. For DFIG wind farms, the initial operating point of each DFIG has an important impact on its fault current and the single-machine should be given an initial slip close to the average slip of all DFIG in the wind farm.Keywords
This publication has 7 references indexed in Scilit:
- Behavior of doubly-fed induction generator under nearby wind plant fault2010
- Modelling wind farms for grid disturbance studiesRenewable Energy, 2008
- Modeling of wind power plants for short circuit analysis in the transmission network2008
- Wind Turbines Based on Doubly Fed Induction Generator Under Asymmetrical Voltage DipsIEEE Transactions on Energy Conversion, 2008
- Comparison of an aggregated model of a wind farm consisting of fixed‐speed wind turbines with field measurementWind Energy, 2007
- Effects of main and leakage flux saturation on the transient performances of doubly-fed wind driven induction generatorElectric Power Systems Research, 2007
- Short-Circuit Current of Wind Turbines With Doubly Fed Induction GeneratorIEEE Transactions on Energy Conversion, 2007