Innovative procedure for measurement of losses of transformers supplying nonsinusoidal loads
Authors:
- 1 January 1999
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 146 (6) , 617-625
Abstract
The measurement of iron-core and copper losses of single-phase transformers is important in particular for transformers feeding nonlinear loads. A new digital data-acquisition method is devised for the separate measurement of iron-core and copper losses of transformers under any full or partial-load condition. The accuracy requirements of the instruments (voltage, current sensors, volt and current meters) employed are addressed. A 25 kVA, 7200/240 V single-phase transformer has been loaded with either three diode-bridge rectifiers and/or a thyristor-bridge rectifier at varying total harmonic voltage and current distortions, such that at the maximum permissible apparent power, losses are identical to the rated losses. The maximum errors of losses are acceptably low if voltage (dividers) and current (shunts) sensors with 2% and digital instruments with 0.1% errors are used. The derating under nonlinear loads is measured as a function of dominant 3rd and 5th current harmonics. The influence of voltage distortion is studied. The total harmonic distortion of the current (THDi) was varied greatly from 0 to 90%, and the resulting voltage THDv values were below 6% for the given power system impedance. At large THDi values (e.g. 90%), the reduction in apparent power rating (RAPR) is not very large (≅ 10%). However, the real power capability (RPC) of the transformer is severely restricted: for example, at THDi = 90% the RPC is about 0.5 pu. For this reason it might be advisable to define derating in terms of the reduction in real power capability and not in terms of RAPR.Keywords
This publication has 3 references indexed in Scilit:
- Modeling of magnetizing and core-loss currents in single-phase transformers with voltage harmonics for use in power flowIEEE Transactions on Power Delivery, 1997
- Computer-aided testing of electrical apparatus supplying nonlinear loadsIEEE Transactions on Power Systems, 1997
- A new computer-aided method for the efficiency measurement of low-loss transformers and inductors under nonsinusoidal operationIEEE Transactions on Power Delivery, 1996