Analysis of Influence of Grid-Following and Grid-Forming Static Var Generators on High-Frequency Resonance in Doubly Fed Induction Generator-Based Wind Farms
Open Access
- 30 September 2024
- journal article
- research article
- Published by MDPI AG in Electronics
- Vol. 13 (19) , 3879
Abstract
In Doubly Fed Induction Generator (DFIG)-based wind farms with Static Var Generators (SVGs), high-frequency resonance will be more like to occur when an unloaded cable is put into operation, which will threaten the stable operation of the wind farm. To address this issue, the influence of power outer loops on the impedance of grid-connected inverters is considered. Based on harmonic linearization, theoretical models for the sequence impedances of DFIGs, Grid-following (GFL) SVGs, and Grid-forming (GFM) SVGs are established. The correctness of the three models is verified by impedance scanning using the frequency sweep method. Through a comparative analysis of these sequence impedances, it is found that unlike the GFM SVG (which exhibits inductive impedance), the GFL SVG exhibits capacitive impedance in the high-frequency band, which leads to negative damping characteristics in the high-frequency band for the wind farm system with the grid-following SVG; thereby, the risk of high-frequency resonance also increases accordingly. On the contrary, GFM control adopted by SVGs can effectively eliminate the negative damping region in the high-frequency band for wind farms to suppress high-frequency resonance. Meanwhile, for grid-forming SVGs, the parameter variations in power synchronous loops have no significant impact on the suppressing effect of high-frequency resonance for wind farms. Finally, an electromagnetic simulation model for a DFIG-based wind farm system with an SVG is established using the StarSim-HIL (hardware-in-the-loop) experiment platform, and the simulation results validate the correctness of the theoretical analysis.Keywords
Funding Information
- State Grid Corporation of China (No. 5500-202329500A-3-2-ZN)
This publication has 27 references indexed in Scilit:
- MMC-STATCOM supplementary wide-band damping control to mitigate subsynchronous control interaction in wind farmsInternational Journal of Electrical Power & Energy Systems, 2022
- An active damping control method for direct-drive wind farm with flexible DC transmission system based on the remodeling of dynamic energy branchesInternational Journal of Electrical Power & Energy Systems, 2022
- Mechanism Analysis and Damping Method for High Frequency Resonance Between VSC-HVDC and the Wind FarmIEEE Transactions on Energy Conversion, 2020
- Small-Signal Modeling and Analysis of DC-Link Dynamics in Type-IV Wind Turbine SystemIEEE Transactions on Industrial Electronics, 2020
- An Enhancing Grid Stiffness Control Strategy of STATCOM/BESS for Damping Sub-Synchronous Resonance in Wind Farm Connected to Weak GridIEEE Transactions on Industrial Informatics, 2019
- Analysis of High-Frequency Resonance in DFIG-Based Offshore Wind Farm via Long Transmission CableIEEE Transactions on Energy Conversion, 2018
- Effect of wind turbine converter control on wind power plant harmonic response and resonancesIET Electric Power Applications, 2017
- Analysis and Active Damping of Multiple High Frequency Resonances in DFIG SystemIEEE Transactions on Energy Conversion, 2016
- A Modified Sequence-Domain Impedance Definition and Its Equivalence to the dq-Domain Impedance Definition for the Stability Analysis of AC Power Electronic SystemsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2016