Investigation of Coordination Limits between SiC-based and IGCT-based SSCBs

Authors:

Abstract
Solid-state circuit breakers (SSCBs) have several advantages over electromechanical circuit breakers for protecting DC microgrids as they can operate much faster, reducing the prospective peak fault current especially at high di/dt. However, protection coordination between multiple SSCBs within a DC microgrid is still under investigation, especially at extremely high-fault-di/dt conditions. High-di/dt protection coordination between two SSCBs depends on the transport delays of the circuit breakers in question, namely the sum of sensing, signal propagation, processing, and switching delays. Earlier work has looked at coordination between SSCBs with similar transport delays. This paper reports on the protection coordination between a Si RB-IGCT-based SSCB and a SiC MOSFET-based SSCB and investigates their protection coordination limits through simulation analysis and testing.