Abstract
The article comprehensively presents the results of research on distribution transformers cellulose insulation models drying with the use of a liquid medium, which is synthetic ester. The tests carried out on laboratory models have shown that the drying efficiency depends, among others, on the initial moisture of the cellulose, the thickness of the cellulose products, the temperature and the moisture of the ester. The article also presents three technologies of working ester treatment contaminated by mineral oil.