The effects of drying time during manufacturing process on partial discharge of 83.3 mva 275/160 kv power transformer
Open Access
- 26 October 2018
- journal article
- research article
- Published by EDP Sciences in MATEC Web of Conferences
- Vol. 218, 04008
Abstract
Power transformer (PT), essential equipment in electrical power system proceeds complicated manufacturing process to meet high standard design. During manufacturing process of PT, the drying stage is of importance to remove excessive moisture contaminant on the solid insulation. This study investigated the effects of drying duration on partial discharge test of 83.3 MVA 275/160 kV PT. The partial discharge test measurements were carried out using IEC 60270 standards comprising of the capacitive network model based on the main quantity apparent charge concept. We found that the lowest partial discharge of 21 pC was achieved at 68 hours drying duration, while the highest value of 60 pC was reached at 81 hours drying time. The longer drying time may lead to initial degradation of cellulose insulation due to excessive heating. The amount of water extracted during drying effect to partial discharge also investigated. We conclude that the drying time at a higher and lower than 68 hours significantly contributes to the increased partial discharge values of PT.Keywords
This publication has 9 references indexed in Scilit:
- Standardized survey of transformer reliability: On behalf of CIGRE WG A2.372017
- Survey of Australian power transformer failures and retirementsIEEE Electrical Insulation Magazine, 2017
- Moisture effect on conductivity of kraft paper immersed in power transformer vegetable‐based insulation oilsIET Generation, Transmission & Distribution, 2017
- Influences of moisture content on surface partial discharge behaviors of oil-impregnated paper insulation under pulsating DC voltage2016
- Moisture in cellulose insulation of power transformers - statisticsIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Degradation of solid dielectrics due to internal partial discharge: some thoughts on progress made and where to go nowIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- Failure analysis of EHV transformersIEEE Transactions on Power Delivery, 1988
- Thermal Ageing of Cellulose Paper InsulationIEEE Transactions on Electrical Insulation, 1977
- Drying and oil impregnation of power transformer insulation1965