Abstract
Distribution lines are generally protected by overcurrent relays. With the integration of inverter-interfaced solar photovoltaic (PV) plant having current limiting feature, fault current seen by the relay on PV-side of that feeder becomes comparable to load current. Conventional overcurrent relaying principle is not suitable for distribution line protection. Distance relay may be a viable option for protection of distribution lines connecting solar PV plant. However, the positive and negative sequence source impedances of PV plant depend on inverter controller which results in limited performance of fixed setting distance relay. This paper proposes an adaptive distance relay setting to protect distribution line connecting PV plant, using prefault voltage and current data at relaying point. The method calculates the positive and negative sequence PV source impedances for boundary setting of distance relay at PV-side. The proposed trip boundary is modified adaptively with the change in prefault conditions of PV plant. Performance of proposed method is tested for different control strategies and operating capacities of PV plant and variation in grid source impedance on a 34-bus distribution system. Real-time application of the proposed method is validated in hardware-in-loop using OPALRT simulators with IEC 61850 as communication protocol and found to be accurate.