A Current Orthogonality Method to Extract Resistive Leakage Current of MOSA
Authors:
- 13 December 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 28 (1) , 93-101
Abstract
A new resistive current extraction method based on orthogonality between the capacitive current and the resistive current (COM) is presented. Orthogonality of the resistive and capacitive current of metal-oxide surge arrester (MOSA) in the low current region is proven. The resistive and capacitive current of MOSA can be obtained accurately, regardless of the harmonic voltage. Several algorithms include the point-on-wave method, the capacitive current compensation method, the harmonic analysis method, and the proposed method are used to extract the resistive current based on simulated voltage and leakage current signal, and to study the influence of MOSA model parameters, capacitance, integral harmonics, and noninteger harmonics of voltage signal, the signal frequency deviation, and the offset in sampling time between current and voltage channels on calculation accuracy. The result indicates that the proposed method has no error if the voltage and current are noiseless, but gives rise to a small error even if the signals have noise. The proposed method is more accurate than other methods. The real voltage and leakage current signals of a 10-kV MOSA are acquired by experiment, and the result indicates that the proposed method is effective and the most stable.Keywords
This publication has 7 references indexed in Scilit:
- Search for new diagnostics for metal oxide surge arrester2002
- Influence of representation model and voltage harmonics on metal oxide surge arrester diagnosticsIEEE Transactions on Power Delivery, 2001
- Diagnostics and monitoring of metal-oxide surge arresters in high-voltage networks-comparison of existing and newly developed proceduresIEEE Transactions on Power Delivery, 2001
- Return voltage measurements on metal oxide surge arresters1999
- Online monitoring of high-voltage metal-oxide surge arresters by wireless passive surface acoustic wave (SAW) temperature sensors1999
- New method for measurement of the resistive leakage currents of metal-oxide surge arresters in serviceIEEE Transactions on Power Delivery, 1990
- Maintenance of surge arrester by a portable arrester leakage current detectorIEEE Transactions on Power Delivery, 1988