Turn Insulation Capability of Large AC Motors Part 2 - Impulse Strength
Authors:
- 1 December 1987
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. EC-2 (4) , 666-673
Abstract
The breakdown voltage of the turn insulation in seventeen motors of various types was measured for 0.1μs risetime impulses. The motors covered a wide range of voltage class, power rating, insulation type, age and winding design. For most motors, the breakdown voltages were 5 pu or higher which is many times the 1.5 pu strength for 0.1 μs surges suggested in an IEEE guideline [1]. Testing of individual coils indicated that some coils had very low breakdown voltages probably due to imperfections acquired during coil forming or stator winding. In general, the withstand strength of the motors was 50 to 100% higher than that of individual coils. The interface between the turn insulation and the groundwall was involved in most failures. Tests on two new motors indicate that manufacturers have the capability to build motors with impulse strengths of 10 pu or more.Keywords
This publication has 6 references indexed in Scilit:
- Turn Insulation Capability of Large AC Motors Part 3 - Insulation CoordinationIEEE Transactions on Energy Conversion, 1987
- Impulse Strength of High Voltage Motor Coil Turn InsulationIEEE Transactions on Energy Conversion, 1986
- Effect of Surge Wave Reflection Inside a Motor On Voltage Distribution Across Stator WindingsIEEE Transactions on Power Apparatus and Systems, 1985
- Investigation of Turn Insulation Failure Mechanisms in Large AC MotorsIEEE Transactions on Power Apparatus and Systems, 1984
- Testing of Electrical Machine Stator Coils Using Sharp-Fronted Impulse VoltageIEEE Transactions on Electrical Insulation, 1984
- Impulse Voltage Strength of AC Rotating MachinesIEEE Transactions on Power Apparatus and Systems, 1981