Abstract
Passive flow manipulation offers an effective route to enhance convective transport in confined air flows where weak mixing and flow maldistribution limit thermal performance. In this study, the effect of triangular vortex generators on flow redistribution and heat transfer is numerically investigated in a confined channel with distributed heat sources. Simulations are performed over a range of inlet velocities (0.5–2.0 m/s) and heat generation rates representative of practical operating conditions. The introduction of vortex generators induces localized flow separation, wake interaction, and enhanced cross-stream mixing, leading to improved penetration of cooling air into otherwise stagnant regions. These flow modifications disrupt thermal boundary layers and promote more uniform temperature fields within the domain. An optimal configuration is identified, yielding a maximum reduction of 7.2 K in peak temperature relative to the baseline case without vortex generators. The results further reveal that excessive blockage deteriorates thermal performance due to restricted flow pathways, highlighting a trade-off between mixing enhancement and flow resistance. Overall, the study demonstrates that strategically placed triangular vortex generators can effectively modulate flow structures and enhance convective heat transfer in confined air cooling systems.

This publication has 61 references indexed in Scilit: